p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PD PZD tel ext
SERVO_S110-DP,
Can be changed: T
SERVO_S110-PN
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Value:
1:
2:
3:
4:
102:
103:
999:
Dependency:
Refer to: p0922
p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PD PZD tel ext
SERVO_S110-DP
Can be changed: T
(EPOS, Pos ctrl),
Data type: Integer16
SERVO_S110-PN
P-Group: Communications
(EPOS, Pos ctrl)
Not for motor type: -
Min
7
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Value:
7:
9:
110:
111:
999:
Dependency:
Refer to: p0922
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Standard telegram 1, PZD-2/2
Standard telegram 2, PZD-4/4
Standard telegram 3, PZD-5/9
Standard telegram 4, PZD-6/14
SIEMENS telegram 102, PZD-6/10
SIEMENS telegram 103, PZD-7/15
Free telegram configuration with BICO
Standard telegram 7, PZD-2/2
Standard telegram 9, PZD-10/5
SIEMENS telegram 110, PZD-12/7
SIEMENS telegram 111, PZD-12/12
Free telegram configuration with BICO
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
999
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
999
Parameter
List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
999