Siemens SINAMICS S110 List Manual page 253

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Dependency:
p1400.4 = 0: upper/lower
p1400.4 = 1: motoring / regenerating
Refer to: p0500, p1520, p1522, p1523, p1532
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values when setting the lower torque limit (p1521 > 0) can result in the motor accelerating in an uncontrol-
lable fashion.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1522[0...n]
CI: Torque limit upper/motoring / M_max upper/mot
SERVO_S110-CAN,
Can be changed: T
SERVO_S110-DP,
Data type: Unsigned32 / FloatingPoint32
SERVO_S110-PN
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for the upper or torque/force limit when motoring.
Dependency:
p1400.4 = 0: upper/lower
p1400.4 = 1: motoring / regenerating
Refer to: p1520, p1521, p1523, p1532
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
p1523[0...n]
CI: Torque limit lower/regenerative / M_max lower/regen
SERVO_S110-CAN,
Can be changed: T
SERVO_S110-DP,
Data type: Unsigned32 / FloatingPoint32
SERVO_S110-PN
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for the lower or torque/force limit when regenerating.
Dependency:
p1400.4 = 0: upper/lower
p1400.4 = 1: motoring / regenerating
Refer to: p1520, p1521, p1522, p1532
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
p1524[0...n]
CO: Torque limit upper/motoring scaling / M_max up/mot scal
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Closed-loop control
Not for motor type: REL
Min
-2000.0 [%]
Description:
Sets the scaling for the upper torque limit or the torque limit when motoring.
Dependency:
p1400.4 = 0: upper/lower
p1400.4 = 1: motoring / regenerating
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: CDS, p0170
Units group: -
Scaling: p2003
Max
-
Calculated: -
Dynamic index: CDS, p0170
Units group: -
Scaling: p2003
Max
-
Calculated: -
Dynamic index: DDS, p0180
Units group: -
Scaling: PERCENT
Max
2000.0 [%]
Parameter
List of parameters
Access level: 3
Func. diagram: 1610, 5620,
5630, 6630
Unit selection: -
Expert list: 1
Factory setting
1520[0]
Access level: 3
Func. diagram: 1610, 5620,
5630
Unit selection: -
Expert list: 1
Factory setting
1521[0]
Access level: 3
Func. diagram: 5620, 5630
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]