Bit field:
Bit
Signal name
00
STO active
01
SS1 active
02
SS2 active
03
SOS active
04
SLS active
05
SOS selected
06
SLS selected
07
Internal event
12
SDI positive selected
13
SDI neg selected
14
ESR retract requested
15
Safety message present
Note:
This parameter is only supplied with actual values in the case of Safety Integrated Extended Functions. For Safety
Integrated Basic Functions (SBC, SS1, STO), the value is equal to zero.
Re bit 07:
An internal event is displayed if a STOP A ... F is active.
r9742.0...15
CO/BO: SI Motion drive-integrated status signals (processor 2) / SI Mtn int st P2
SERVO_S110-CAN,
Can be changed: -
SERVO_S110-DP,
Data type: Unsigned32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Status signal for safety-relevant motion monitoring functions integrated in the drive.
Bit field:
Bit
Signal name
00
STO active
01
SS1 active
02
SS2 active
03
SOS active
04
SLS active
07
Internal event
09
Active SLS stage bit 0
10
Active SLS stage bit 1
11
SOS selected
12
SDI pos active
13
SDI neg active
15
SSM (speed below limit value)
Notice:
Re bit 07:
An internal event is displayed if a STOP A ... F is active.
The signal state behaves in an opposite way to the PROFIsafe Standard.
Note:
This parameter is only supplied with actual values in the case of Safety Integrated Extended Functions. For Safety
Integrated Basic Functions (SBC, SS1, STO), the value is equal to zero.
r9744
SI message buffer changes, counter / SI msg_buffer chng
SERVO_S110-CAN,
Can be changed: -
SERVO_S110-DP,
Data type: Unsigned16
SERVO_S110-PN
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the changes of the safety message buffer. This counter is incremented every time that the safety message
buffer changes.
Recommend.:
This is used to check whether the safety message buffer has been read out consistently.
Dependency:
Refer to: r9747, r9748, r9749, p9752, r9753, r9754, r9755, r9756
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
No
Set
Set
Yes
Yes
Yes
Yes
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
Parameter
List of parameters
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
Yes
-
Not set
-
Not set
-
No
-
No
2861
No
2861
No
2860
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
1-597

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents