Parameter
List of parameters
p1240 = 2, 3:
When the lower DC link voltage threshold is reached (p1248), the following applies:
- the Vdc_min controller limits the energy taken from the DC link in order to keep the DC link voltage above the min-
imum DC link voltage when accelerating.
- the motor is braked in order to use its kinetic energy to buffer the DC link.
p1240 = 4, 5, 6:
When the threshold in p1244 or p1248 is reached, the DC link voltage monitoring initiates a fault with a response
and therefore reduces additional negative effects on the DC link voltage.
p1240 = 7, 9:
As for p1240 = 1, 3. However, the motor is prevented from accelerating due to the fact that other drives are regen-
erating. The effective lower torque limit cannot exceed the offset of the torque limit (p1532).
p1240 = 8, 9:
As for p1240 = 2, 3. However, the motor is prevented from braking due to the fact that the DC link voltage has been
lowered. The effective upper torque limit cannot be less than the offset of the torque limit (p1532).
p1244[0...n]
DC link voltage threshold upper / Vdc upper thresh
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Functions
Not for motor type: REL
Min
165 [V]
Description:
Sets the upper threshold for the DC link voltage.
For p1240 = 1, 3, 7, 9, this threshold is used as limit setpoint for the Vdc_max controller.
For p1240 = 4, 6, for DC link voltages above this threshold, an appropriate fault is output.
Dependency:
Refer to: p1240, p1248, p1250
Note:
For p1244 < 1.07 * "parameterized DC link voltage" input of values is rejected.
For p0204.0 = 1, the following applies:
"Parameterized DC link voltage" = p0210
For p0204.0 = 0, the following applies:
"Parameterized DC link voltage" = p0210 * 1.4142
p1248[0...n]
DC link voltage threshold lower / Vdc lower thresh
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Functions
Not for motor type: REL
Min
100 [V]
Description:
Sets the lower threshold for the DC link voltage.
For p1240 = 2, 3, 8, 9, this threshold is used as limit setpoint for the Vdc_min controller.
For p1240 = 5, 6, for DC link voltages below this threshold, an appropriate fault is output.
Dependency:
Refer to: p1240, p1244, p1250
Note:
For p1248 > 0.93 * "parameterized DC link voltage" input of values is rejected.
For p0204.0 = 1, the following applies:
"Parameterized DC link voltage" = p0210
For p0204.0 = 0, the following applies:
"Parameterized DC link voltage" = p0210 * 1.4142
1-230
Calculated: CALC_MOD_CON
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
1200 [V]
Calculated: CALC_MOD_CON
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
1000 [V]
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: 5650
Unit selection: -
Expert list: 1
Factory setting
750 [V]
Access level: 3
Func. diagram: 5650
Unit selection: -
Expert list: 1
Factory setting
450 [V]