Parameter
List of parameters
Note:
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
For p9568 = p9368 = 0, the following applies:
The value in p9546/p9346 (SSM) is applied as the velocity limit for SAM.
p9370
SI Motion acceptance test mode (processor 2) / SI Mtn acc_mod P2
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Setting to select and de-select the acceptance test mode.
Value:
0:
172:
Dependency:
Refer to: p9358, r9371
Refer to: C01799
Note:
Acceptance test mode can only be selected if the motion monitoring functions, which are integrated in the drives,
are enabled (p9601.2/p9801.2).
r9371
SI Motion acceptance test status (processor 2) / SI Mtn acc_stat P2
SERVO_S110-CAN,
Can be changed: -
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Displays the status of the acceptance test mode.
Value:
0:
12:
13:
15:
172:
Dependency:
Refer to: p9358, p9370
Refer to: C01799
p9380
SI Motion pulse suppression delay bus failure (processor 2) / SI Mtn t to IL P2
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the delay time after which the pulses are safely suppressed after a bus failure.
Dependency:
Refer to: p9363
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
1-546
[00 hex] De-select the acceptance test mode
[AC hex] Select the acceptance test mode
[00 hex] Acc_mode inactive
[0C hex] Acc_mode not possible due to POWER ON fault
[0D hex] Acc_mode not possible due to incorrect ID in p9370
[0F hex] Acc_mode not possible due to expired Acc_timer
[AC hex] Acc_mode active
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
00AC hex
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
00AC hex
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
800000.00 [µs]
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]