Siemens SINAMICS S110 List Manual page 473

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

p4821
Function generator period / FG period duration
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Trace and function generator
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the period of the signal to be generated for the function generator.
Dependency:
Ineffective when p4820 = 4 (PRBS).
p4822
Function generator pulse width / FG pulse width
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Trace and function generator
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the pulse width for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 1 (square-wave).
p4823
Function generator bandwidth / FG bandwidth
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Trace and function generator
Not for motor type: -
Min
0.0025 [Hz]
Description:
Sets the bandwidth for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 4 (PRBS).
Refer to: p4830
Refer to: A02041
p4824
Function generator amplitude / FG amplitude
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Trace and function generator
Not for motor type: -
Min
-1600.00 [%]
Description:
Sets the amplitude for the signal to be generated for the function generator.
Dependency:
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
60000.00 [ms]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
60000.00 [ms]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
16000.0000 [Hz]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
1600.00 [%]
Parameter
List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
1000.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
500.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
4000.0000 [Hz]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
5.00 [%]