Parameter
List of parameters
p1047[0...n]
Motorized potentiometer ramp-up time / Mop ramp-up time
SERVO_S110-CAN
Can be changed: U, T
(Extended set),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Setpoints
(Extended set),
Not for motor type: -
SERVO_S110-PN
(Extended set)
Min
0.000 [s]
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1048, p1082
Note:
When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
p1048[0...n]
Motorized potentiometer ramp-down time / Mop ramp-down time
SERVO_S110-CAN
Can be changed: U, T
(Extended set),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Setpoints
(Extended set),
Not for motor type: -
SERVO_S110-PN
(Extended set)
Min
0.000 [s]
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1047, p1082
Note:
The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
r1050
CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
SERVO_S110-CAN
Can be changed: -
(Extended set),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Setpoints
(Extended set),
Not for motor type: -
SERVO_S110-PN
(Extended set)
Min
- [rpm]
Description:
Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Recommend.:
Interconnect the signal with main setpoint (p1070).
Dependency:
Refer to: p1070
Note:
For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
cancel pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
1-196
Calculated: -
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
1000.000 [s]
Calculated: -
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
1000.000 [s]
Calculated: -
Dynamic index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 2
Func. diagram: 3020
Unit selection: -
Expert list: 1
Factory setting
10.000 [s]
Access level: 2
Func. diagram: 3020
Unit selection: -
Expert list: 1
Factory setting
10.000 [s]
Access level: 3
Func. diagram: 1550, 3020
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]