Parameter
List of parameters
p0759
CU analog input characteristic value x2 / CU AI char x2
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Terminals
Not for motor type: -
Min
-11.000 [V]
Description:
Sets the scaling characteristic for the analog input.
The scaling characteristic for the analog input is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V) of the 2nd value pair of the characteristic.
Note:
The parameters for the characteristic do not have a limiting effect.
p0760
CU analog input characteristic value y2 / CU AI char y2
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Terminals
Not for motor type: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog input.
The scaling characteristic for the analog input is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Note:
The parameters for the characteristic do not have a limiting effect.
p0763
CU analog input offset / CU AI offset
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Terminals
Not for motor type: -
Min
-20.000 [V]
Description:
Sets the offset for the analog input.
The offset is added to the input signal before the scaling characteristic.
p0766
CU analog input activate absolute value generation / CU AI absVal act
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: Integer16
CU_S110-PN
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Activates the absolute value generation of the analog input signal.
Value:
0:
1:
1-150
No absolute value generation
Absolute value generation switched in
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
11.000 [V]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
20.000 [V]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
1
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 2
Func. diagram: 2040
Unit selection: -
Expert list: 1
Factory setting
10.000 [V]
Access level: 2
Func. diagram: 2040
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 2040
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 3
Func. diagram: 2040
Unit selection: -
Expert list: 1
Factory setting
0