p2030
Field bus int protocol selection / Field bus protocol
CU_S110-CAN
Can be changed: T
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
4:
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2030
Field bus int protocol selection / Field bus protocol
CU_S110-DP
Can be changed: T
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
1:
3:
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
r2032
Master control, control word effective / PcCtrl STW eff
SERVO_S110-CAN,
Can be changed: -
SERVO_S110-DP,
Data type: Unsigned16
SERVO_S110-PN
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the effective control word 1 (STW1) of the drive for the master control.
Bit field:
Bit
Signal name
00
ON/OFF1
01
OC / OFF2
02
OC / OFF3
03
Operation enable
04
Ramp-function generator enable
05
Start ramp-function generator
06
Speed setpoint enable
07
Acknowledge fault
08
Jog bit 0
09
Jog bit 1
10
Master ctrl by PLC
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be trans-
ferred from another automation device.
Note:
OC: Operating condition
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
No protocol
CAN
No protocol
USS
PROFIBUS
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
4
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
3
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameter
List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
4
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
3
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
3030
No
3030
No
-
1-289