Siemens SINAMICS S110 List Manual page 261

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

p1585[0...n]
Flux actual value, smoothing time / Flux actVal T_smth
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Closed-loop control
Not for motor type: PEM, REL
Min
0 [ms]
Description:
Sets the smoothing time for the flux actual value.
p1590[0...n]
Flux controller P gain / Flux controller Kp
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Closed-loop control
Not for motor type: PEM, REL
Min
0.0 [A/Vs]
Description:
Sets the proportional gain for the flux controller.
Note:
For synchronous motors, this parameters has no effect.
The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
p1592[0...n]
Flux controller integral time / Flux controller Tn
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Closed-loop control
Not for motor type: PEM, REL
Min
0 [ms]
Description:
Sets the integral time for the flux controller.
Note:
For synchronous motors, this parameters has no effect.
The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
p1612[0...n]
Current setpoint, open-loop control, encoderless / I_setCtrEncoderl
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Closed-loop control
Not for motor type: -
Min
0.00 [Arms]
Description:
Sets the current setpoint for controlled (open-loop) encoderless operation.
Note:
The value is effective at speeds less than p1755 and represents a reserve for a possibly existing load torque or
torque error in the moment of inertia.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: CALC_MOD_CON
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
1000 [ms]
Calculated: CALC_MOD_CON
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
999999.0 [A/Vs]
Calculated: CALC_MOD_CON
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
10000 [ms]
Calculated: CALC_MOD_REG
Dynamic index: DDS, p0180
Units group: 6_2
Scaling: -
Max
10000.00 [Arms]
Parameter
List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 3
Func. diagram: 5722
Unit selection: -
Expert list: 1
Factory setting
10.0 [A/Vs]
Access level: 3
Func. diagram: 5722
Unit selection: -
Expert list: 1
Factory setting
30 [ms]
Access level: 2
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
0.00 [Arms]