Siemens SINAMICS S110 List Manual page 134

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Parameter
List of parameters
Note:
When using a Terminal Module 31 (TM31), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using CO: r4105.
p0604[0...n]
Motor temperature alarm threshold / Mot_temp al thr
SERVO_S110-CAN,
Can be changed: C2(3), U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: -
Min
0.0 [°C]
Description:
Sets the alarm threshold for monitoring the motor temperature.
Dependency:
Refer to: p0606
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis for canceling the alarm is 2 Kelvin.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
p0605[0...n]
Motor temperature fault threshold / Mot_temp flt thr
SERVO_S110-CAN,
Can be changed: C2(3), U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: -
Min
0.0 [°C]
Description:
Sets the fault threshold for monitoring the motor temperature.
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis for canceling the fault is 2 Kelvin.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
p0606[0...n]
Motor temperature timer / Mot_temp timer
SERVO_S110-CAN,
Can be changed: C2(3), U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: -
Min
0.000 [s]
Description:
Sets the timer for the alarm threshold for the motor temperature monitoring function.
This timer is started when the temperature alarm threshold (p0604) is exceeded.
If the timer expires before the temperature in the meantime falls below the alarm threshold, the fault F07011 is out-
put.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer has expired, then fault F07011
is immediately output.
As long as the motor temperature has still not exceeded the fault threshold and the alarm thresholds have again
been undershot, the fault can be acknowledged.
Dependency:
Refer to: p0604, p0605
Refer to: F07011, A07910
1-134
Calculated: -
Dynamic index: MDS, p0130
Units group: 21_1
Scaling: -
Max
200.0 [°C]
Calculated: -
Dynamic index: MDS, p0130
Units group: 21_1
Scaling: -
Max
200.0 [°C]
Calculated: -
Dynamic index: MDS, p0130
Units group: -
Scaling: -
Max
600.000 [s]
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 2
Func. diagram: 8016
Unit selection: p0505
Expert list: 1
Factory setting
120.0 [°C]
Access level: 2
Func. diagram: 8016, 8017
Unit selection: p0505
Expert list: 1
Factory setting
145.0 [°C]
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
240.000 [s]