Re bit 03:
The hysteresis is set in p2150.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
r2198.4...12
CO/BO: Status word monitoring 2 / ZSW monitor 2
SERVO_S110-CAN,
Can be changed: -
SERVO_S110-DP,
Data type: Unsigned16
SERVO_S110-PN
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the second status word for monitoring functions.
Bit field:
Bit
Signal name
04
|n_set| < p2161
05
n_set > 0
06
Motor stalled
10
|M_set| < torque threshold value 1
11
Load monitoring signals an alarm
12
Load monitoring signals a fault condition
Note:
Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
r2199.0...11
CO/BO: Status word monitoring 3 / ZSW monitor 3
SERVO_S110-CAN,
Can be changed: -
SERVO_S110-DP,
Data type: Unsigned16
SERVO_S110-PN
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the third status word for monitoring functions.
Bit field:
Bit
Signal name
00
|n_act| < speed threshold value 3
01
f or n comparison value reached or
exceeded
04
Speed setp - act val deviation in tolerance
t_on
05
Ramp-up/ramp-down completed
06
Current below the zero current threshold
11
Torque utilization < torque threshold value 2 Yes
Note:
Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit will never be reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Parameter
List of parameters
Access level: 2
Func. diagram: 1530, 2536
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
FP
No
8010
No
8010
No
8012
No
8012
No
8013
No
8013
Access level: 2
Func. diagram: 1530, 2537
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
FP
No
8010
No
8010
No
8010
No
8010
No
-
No
8012
1-335

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents