Parameter
List of parameters
p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PD PZD tel ext
SERVO_S110-DP
Can be changed: T
(Pos ctrl),
Data type: Integer16
SERVO_S110-PN
P-Group: Communications
(Pos ctrl)
Not for motor type: -
Min
999
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Value:
999:
Dependency:
Refer to: p0922
p2080[0...15]
BI: Binector-connector converter status word 1 / Bin/con ZSW1
All objects
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Communications
Not for motor type: -
Min
-
Description:
Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form status word 1.
Index:
[0] = Bit 0
[1] = Bit 1
[2] = Bit 2
[3] = Bit 3
[4] = Bit 4
[5] = Bit 5
[6] = Bit 6
[7] = Bit 7
[8] = Bit 8
[9] = Bit 9
[10] = Bit 10
[11] = Bit 11
[12] = Bit 12
[13] = Bit 13
[14] = Bit 14
[15] = Bit 15
Dependency:
Refer to: p2088, r2089
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
1-306
Free telegram configuration with BICO
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
999
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 3
Func. diagram: 2472
Unit selection: -
Expert list: 1
Factory setting
0