Siemens SINAMICS S110 List Manual page 314

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Parameter
List of parameters
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2101
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- if there is no existing fault number.
- the message type is not "fault" (F).
- when a fault is present.
p2101[0...19]
Setting the fault response / Fault response
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: Messages
Not for motor type: -
Min
0
Description:
Sets the fault response for the selected fault.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
It is not possible to re-parameterize the response to a specific fault for faults that are already present (queued).
Note:
The fault response can only be changed for faults with the appropriate identification (see the List Manual, chapter
"Faults and alarms").
Example:
F12345 and fault response = OFF3 (OFF1, OFF2, NONE)
--> The default fault response OFF3 can be changed to OFF1, OFF2 or NONE.
Re value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
Re value = 2 (OFF2):
Internal/external pulse inhibit.
Re value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
Re value = 5 (STOP2):
n_set = 0
Re Value = 6 (DCBRK):
The value can only be set for all motor data sets when p1231 = 3, 4.
a) This function is not supported for synchronous motors (p0300 = 2xx, 4xx).
b) For induction motors (p0300 = 1xx), the DC braking is initiated.
Re value = 7 (ENCODER (p0491)):
The fault response set in p0491 is executed if applicable.
p2102
BI: Acknowledge all faults / Ackn all faults
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: Unsigned32 / Binary
CU_S110-PN
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the signal source to acknowledge all faults at all drive objects of the drive system.
1-314
NONE
OFF1
OFF2
OFF3
STOP1 (being developed)
STOP2
DC braking
ENCODER (p0491)
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
7
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: 1750, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2546, 8060
Unit selection: -
Expert list: 1
Factory setting
0