r1199.0...6
CO/BO: Ramp-function generator status word / RFG ZSW
SERVO_S110-CAN
Can be changed: -
(Extended set),
Data type: Unsigned16
SERVO_S110-DP
(Extended set),
P-Group: Setpoints
SERVO_S110-PN
Not for motor type: -
(Extended set)
Min
-
Description:
Displays the status word for the ramp-function generator (RFG).
Bit field:
Bit
Signal name
00
Ramp-up active
01
Ramp-down active
02
RFG active
03
Ramp-function generator set
04
Ramp-function generator held
05
Ramp-function generator tracking active
06
Maximum limit active
Note:
Re bit 02:
The bit is an OR logic operation - bit 00 and bit 01.
p1206[0...9]
Set the fault number without automatic restart / Fault_No w/o AR
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: Unsigned16
SERVO_S110-PN
P-Group: Functions
Not for motor type: -
Min
0
Description:
Selects the faults for which automatic restart should not be effective.
Dependency:
The setting is only effective for p1210 = 6, 16.
Refer to: p1210
p1208[0...1]
BI: AR modification infeed / AR modification
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: Unsigned32 / Binary
SERVO_S110-PN
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source to modify the automatic restart (AR).
Interconnections between the automatic restart and infeed:
With the following interconnection in the mode p1210 = 6, the automatic restart can respond to infeed faults:
BI: p1208[0] = r2139.3
With the following interconnection, in the mode p1210 = 4, the automatic restart can respond to line supply failure of
the infeed:
BI: p1208[1] = r0863.2
Index:
[0] = Infeed fault
[1] = Infeed line supply failure
Dependency:
Refer to: r0863, r2139
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
65535
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
Parameter
List of parameters
Access level: 3
Func. diagram: 1550, 3080,
8010
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
1-215