p9518
SI motion encoder pulses per revolution (processor 1) / SI Mtn puls/rev P1
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: Unsigned32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the number of encoder pulses per revolution for rotary motor encoders.
The encoder that is used for the safe motion monitoring functions on processor 1 must be parameterized in this
parameter.
Dependency:
Refer to: p0408, p9516
Refer to: F01671
Note:
For safety functions that have not been enabled (p9501 = 0), the following applies: When booting, p9518 is auto-
matically set the same as p0408.
For safety functions that are enabled (p9501 > 0), the following applies: p9518 is checked whether it coincides with
p0408.
p9519
SI Motion fine resolution G1_XIST1 (processor 1) / SI Mtn G1_XIST1 P1
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: Unsigned32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
2
Description:
Sets the fine resolution for G1_XIST1 in bits.
The encoder that is used for the safe motion monitoring functions on processor 1 must be parameterized in this
parameter.
Dependency:
Refer to: p0418
Refer to: F01671
Note:
For safety functions that have not been enabled (p9501 = 0), the following applies: When booting, p9519 is auto-
matically set the same as p0418.
For safety functions that are enabled (p9501 > 0), the following applies: p9519 is checked whether it coincides with
p0418.
G1_XIST1: Encoder 1 position actual value 1 (PROFIdrive)
p9520
SI Motion spindle pitch (processor 1) / SI Mtn Sp_pitch P1
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0.1000 [mm]
Description:
Sets the gear ratio between the encoder and load in mm/revolution for a linear axis with rotary encoder.
Notice:
The fourth decimal point can be rounded-off depending on the size of the entered number (from 3 places before the
decimal point).
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
16777215
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
18
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
8388.0000 [mm]
Parameter
List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2048
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
11
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.0000 [mm]