18
DI 18 (X130.4)
19
DI 19 (X130.5)
20
DI 20 (X131.1)
21
DI 21 (X131.2)
22
DI 22 (X131.4)
Dependency:
The simulation of a digital input is selected using p0795.
Refer to: p0795
Notice:
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
p0797
CU analog input simulation mode / CU AI sim_mode
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: Integer16
CU_S110-PN
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Sets the simulation mode for the analog input.
Value:
0:
1:
Dependency:
The setpoint for the input voltage is specified via p0798.
Refer to: p0798
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p0798
CU analog input simulation mode setpoint / CU AI sim setp
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Terminals
Not for motor type: -
Min
-20.000 [V]
Description:
Sets the setpoint for the input value in the simulation mode of the analog input.
Dependency:
The simulation of an analog input is selected using p797.
If AI is parameterized as voltage input (p756), then the setpoint is a voltage in V.
If AI is parameterized as current input (p756), then the setpoint is current in mA.
Refer to: p0756, p0797
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p0799[0...2]
CU inputs/outputs, sampling time / CU I/O t_sampl
CU_S110-CAN,
Can be changed: C1(3)
CU_S110-DP,
Data type: FloatingPoint32
CU_S110-PN
P-Group: Commands
Not for motor type: -
Min
1000.00 [µs]
Description:
Sets the sampling time for the inputs and outputs of the Control Unit.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
No simulation mode for analog input x
Simulation mode for analog input x
High
High
High
High
High
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
20.000 [V]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
5000.00 [µs]
Parameter
List of parameters
Low
-
Low
-
Low
-
Low
-
Low
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 3
Func. diagram: 2020, 2030,
2031
Unit selection: -
Expert list: 1
Factory setting
4000.00 [µs]