Parameter
List of parameters
p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
SERVO_S110-CAN,
Can be changed: T
SERVO_S110-DP,
Data type: Unsigned32 / Binary
SERVO_S110-PN
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enables the ramp-function generator.
Dependency:
Refer to: p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1141[0...n]
BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
SERVO_S110-CAN,
Can be changed: T
SERVO_S110-DP,
Data type: Unsigned32 / Binary
SERVO_S110-PN
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continues the ramp-function generator.
Dependency:
Refer to: p1140, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
p1142[0...n]
BI: Enable setpoint/inhibit setpoint / Setpoint enable
SERVO_S110-CAN,
Can be changed: T
SERVO_S110-DP,
Data type: Unsigned32 / Binary
SERVO_S110-PN
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
1-208
Calculated: -
Dynamic index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dynamic index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dynamic index: CDS, p0170
Units group: -
Scaling: -
Max
-
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: 2501
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2501
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2501
Unit selection: -
Expert list: 1
Factory setting
1