Siemens SINAMICS S110 List Manual page 543

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SS1: Safe Stop 1
p9360
SI Motion pulse suppression shutdown speed (Motor Module) / SI Mtn IL n_sh MM
SERVO_S110-CAN
Can be changed: C2(95)
(Safety rot),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Safety Integrated
(Safety rot),
Not for motor type: -
SERVO_S110-PN
(Safety rot)
Min
0.00 [rpm]
Description:
Sets the shutdown speed for the pulse suppression.
Below this speed "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP
A).
Dependency:
Refer to: p9356, p9560
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SS1: Safe Stop 1
p9363[0...3]
SI Motion SLS stop response (processor 2) / SI Mtn SLS stop P2
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the stop response for the function "Safely-Limited Speed" (SLS).
These settings apply to the individual limit values for SLS.
In the case of encoderless motion monitoring (p9306 = 1), only a value of 0 or 1 is permitted.
Value:
0:
1:
2:
3:
4:
10:
11:
12:
13:
14:
Index:
[0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLP4
Dependency:
Refer to: p9331, p9380, p9563
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The values 4 and 14 are not supported on Control Unit 305.
SLS: Safely-Limited Speed
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
STOP A
STOP B
STOP C
STOP D
STOP E
STOP A with delayed pulse suppression when the bus fails
STOP B with delayed pulse suppression when the bus fails
STOP C with delayed pulse suppression when the bus fails
STOP D with delayed pulse suppression when the bus fails
STOP E with delayed pulse suppression when the bus fails
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
6000.00 [rpm]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
14
Parameter
List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [rpm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2
1-543