Lucent Technologies SLC ConnectReach User & Service Manual page 146

Access system
Table of Contents

Advertisement

®
Configuring the SLC
ConnectReach
Using the Configuration Commands
Configuring the Channel Bank Mode
(Continued)
Procedure (continued)
4-60
Issue 4
June 2002
System
Step
Procedure
To assign DS0s manually, enter the Cross-connect command from the
9
channel-bank prompt and then enter one of the following submenu
commands.
To
Enable cross-connect
Assign a DS0 to a line
Show settings
Access online assistance Help
Example:
If the SLC ConnectReach system is equipped with one FXS eight port board and
one FXO eight port board and the customer's site uses two FXS lines and one
FXO line, the configuration steps would be as follows:
1.
Enter the following commands at the config:Channel-bank:Cross-connect
prompt:
(config:Channel-bank:Cross-connect) > enable on
(config:Channel-bank:Cross-connect) > set-DS0-to-line
(config:Channel-bank:Cross-connect) > set-DS0-to-line
(config:Channel-bank:Cross-connect) > set-DS0-to-line
2.
To view the settings, enter the show-all command.
(config:Channel-bank:Cross-connect) > show-all
DS0
Line
1
1
2
2
3
9
3.
To clear a DS0 setting, enter zero for the line.
(config:Channel-bank:Cross-connect) > set-DS0-to-line
Enter this
...and one of these options
command...
[off], on
enable
DS0 (1...24) Line (0...24)
set-DS0-to-line
Show-all
363-208-050
1
1
2
2
3
9
3
0
(Continued on next page)