4.4.2 Force DO on

You can switch to the Diagnosis mode by the following steps. Set P2.008 to 406 to force enable
the DO mode. Then, set the DO by binary method with P4.006. When the parameter value is 2,
4
it forces DO2 on. When the value is 5, it forces DO1 and DO3 on. No data is retained in this
mode. The mode returns to the normal DO mode after power cycling of the drive. You can also
set P2.008 to 400 to switch to the normal DO mode.
Note: P4.006 is displayed in hexadecimal format. Therefore, it does not show the fifth 0.
4-12
S
S
Force enable the
DO mode
S
Force DO1 on
Force DO2 on
Force DO3 on
Force DO4 on
Force DO5 on
Force DO1 and DO3 on
Force DO1, DO2, and DO3 on