Table 8.3 Monitoring variables descriptions
Description of monitoring variables:
Item
Monitoring
code
Format
Category
Monitoring
method
Panel
display
Mapping
The property code of each monitoring variable is described in the following table:
Property
B
D1 D2
Dec
Hex
Each monitoring variable has a code, and you can set the code to P0.002 and monitor
the variable.
Each monitoring variable is stored in the 32-bit format (long integer) in the servo drive.
Basic variables / extension variables:
1. Basic variables: variables (P0.002 = 0 to 31) within the loop of pressing the UP /
DOWN keys; in monitoring mode, use the UP / DOWN keys on the panel to display
the variables.
2. Extension variables: variables other than basic variables.
Panel display / mapping:
1. Panel display: monitor with the panel
2. Mapping: monitor variables or parameters by mapping parameters
1. Use the MODE key to switch to the monitoring mode and press the UP / DOWN keys
to select the variable to monitor.
2. Input the code of the variable to be monitored into P0.002 and start monitoring.
Press the SHIFT key on the panel to switch between high and low digit display;
press the SET key on the panel to switch between decimal and hexadecimal display.
1. Parameters that support monitoring variable mapping: P0.009 - P0.013. Refer to
Section 8.3 Parameter descriptions.
2. Read the monitoring variables through communication using mapping parameters.
3. The values of the mapping parameters (P0.009 - P0.013) are the content of the
basic variables (17h, 18h, 19h, and 1Ah). To monitor P0.009, set P0.017 to the
value to read (refer to P0.002). Read the data specified by P0.017 through
communication or with the panel (set P0.002 to 23). When the panel displays
"VAR-1", it then displays the content value of P0.009.
BASE: basic variables. Select the variables with the UP / DOWN keys on the panel.
Decimal place displayed on the panel: D1 indicates 1 decimal place and D2 indicates 2
decimal places.
Only decimal display is available on the panel, and you cannot switch to hexadecimal
display by pressing the SET key.
Only hexadecimal display is available on the panel, and you cannot switch to decimal
display by pressing the SET key.
Description
Description
Parameters
8
8-281