X: additional function for Capture
Bit
8
1 to 3
Z: additional function for Compare
Bit
0
1 to 3
P1.020
Default: 0
Format: DEC
Settings:
When the Capture function is enabled and set to capture multiple points (P5.038 > 1), use this
parameter to set the range within which the system stops receiving the DI captured signal once the data
is captured. The DI captured signal received within this range is not recognized as valid. Use this
function to prevent the system from seeing noise as effective signals within the non-capture range.
8-56
Function
Set this bit to 0 to disable this function. When the number of capturing times
(P5.038) is 0, capturing is complete.
Cycle
0
Set this bit to 1 to enable this function. When the number of capturing times
mode
(P5.038) is 0, the servo drive automatically resets the number of capturing
times to the default setting.
Reserved
-
Function
Set this bit to 0 to disable this function. The value of P1.024 remains after the
P1.024 is
comparing is complete.
reset to 0
Set this bit to 1 to enable this function. P1.024 automatically resets to 0 after
automatically
taking effect once.
Reserved
-
Capture: masking range
Unit: Pulse unit of capture source
P1.020 masking
pulse number
The system activates the masking area after capturing this mark.
Description
Description
Control mode: All
Setting range: 0 to +100000000
Data size: 32-bit
P1.020 masking
pulse number
Masking area
ASDA-A3
Address: 0128H
0129H