ASDA-A3
P1.066
Operation
Panel / software
interface:
Default: 0.0
Unit: 1 cycle
Format: One decimal
Setting range: 0.0 to 200.0
Example: 1.5 = 1.5 cycles
Settings:
Rotation number setting when the maximum voltage (10V) is input to the analog Position command. If
the setting on the panel is 3.0 and the external voltage input is +10V, then the Position command is +3
cycles. If the input is +5V, then the Position command is +1.5 cycles. If the input is -10V, then the
Position command is -3 cycles.
Position control command = Input voltage x Set value / 10
P1.067
P1.068
Default: 4
Unit: ms
Format: DEC
Settings:
0: disable this function.
The moving filter smooths the beginning and end of the step command, but it also delays the command.
P1.069 -
P1.071
Analog Position command - maximum cycle number
Communication
0
0.1 cycle
DEC
0 to 2000
15 = 1.5 cycles
Reserved
Position command - moving filter
Original Position
command
Holding time
Reserved
Control mode: PT
Data size: 16-bit
-
-
-
-
-
-
-
-
Control mode: PT / PR
Setting range: 0 to 100
Data size: 16-bit
Command that has gone
through moving filter
Parameters
Address: 0184H
0185H
Address: 0188H
0189H
8
8-77