Chapter 4 Display and Operation|ASDA-A2 Series
Figure 4.4

4.4.3 Force Output Control Operation

For testing, the digital outputs can be forced to be activated (ON) or inactivated (OFF) by using
parameter P2-08 and P4-06. First, set P2-08 to 406 to enable the force output control function and then
using P4-06 to force the digital outputs to be activated. Follow the setting method in Figure 4.6 to enter
into Force Output Control operation mode. When P4-06 is set to 2, the digital output, DO2 is activated.
When P4-06 is set to 5, the digital outputs, DO1 and DO3 are both activated. The parameter setting
value of P4-06 is not retained when power is off. After re-power the servo drive, all digital outputs will
return to the normal status. If P2-08 is set to 400, it also can switch the Force Output Control operation
mode to normal Digital Output (DO) Control operation mode.
1The DO function and status is determined by P2-18 to P2-22. This function is enabled only when
Servo Off (the servo drive is disabled).
4-8