When the screen displays:
Emergency stop warning:
Check if any of the digital inputs DI1 - DI10 are set to emergency stop (EMGS).
Corrective action:
If you do not want to set the emergency stop (EMGS) as one of the digital inputs,
1.
make sure none of the digital inputs DI1 - DI10 are set to emergency stop (EMGS)
(make sure that none of the parameters, P2.010 - P2.017, P2.036, and P2.037,
are set to 21).
If the emergency stop (EMGS) function is needed, make sure this DI is on when it is
2.
preset as normally closed (function code: 0x0021), and then set this DI as normally
open (function code: 0x0121).
When the screen displays:
Negative limit error warning:
Check if any of the digital inputs DI1 - DI10 are set to negative limit (NL) and that DI is not
on.
Corrective action:
If you do not want to set the negative limit (NL) as one of the digital inputs, make
1.
sure none of the digital inputs DI1 - DI10 are set to negative limit (NL) (make sure
that none of the parameters, P2.010 - P2.017, P2.036, and P2.037, are set to 22).
If the negative limit (NL) function is needed, make sure this DI is on when it is preset
2.
as normally closed (function code: 0x0022), and then set this DI as normally open
(function code: 0x0122).