Force Do On - Delta ASDA-B3 Series User Manual

Hide thumbs Also See for ASDA-B3 Series:
Table of Contents

Advertisement

ASDA-B3

4.4.2 Force DO on

You can switch to the Diagnosis mode by the following steps. Set P2.008 to 406 and enable the
function to force DO on. Then, set the DO by binary method with P4.006. When the parameter
value is 2, it forces DO2 on. When the value is 5, it forces DO1 and DO3 on. No data is retained
in this mode. The mode returns to the normal DO mode after cycling the power. You can also
set P2.008 to 400 to switch to the normal DO mode.
Note: P4.006 is displayed in hexadecimal format. Therefore, it does not show the fifth 0.
SET
SET
Force to enable
DO mode
SET
Force DO1 on
Force DO2 on
Force DO3 on
Force DO4 on
Force DO5 on
Force DO1 and DO3 on
Force DO1, DO2, and DO3 on
Test Operation and Panel Display
4
4-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents