DS1 CO Dial Tone Seizure Test (#314)
DS1 CO Dial Tone Seizure Test checks the trunk's signaling capability provided by
the DS1 Interface circuit pack. The maintenance software initiates the test by
sending a ''seizure'' message to the DS1 Interface circuit pack and expects an
''active'' reply from the DS1 interface circuit pack. If the ''active'' message is
received, then the test passes. If no message is received and the timer expires,
the test is aborted. If the DS1 Interface circuit pack sends a ''reorder'' message
back to maintenance software, then the test fails.
This test cannot be run on a trunk in any of the following conditions:
The trunk direction is administered as an incoming only trunk.
The trunk has been seized by a normal trunk call.
The trunk is administered with maintenance test disabled.
Table 213. TEST #314 DS1 CO Dial Tone Seizure Test
Error
Test
Code
Result
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1000
ABORT
System resources required to run this test are not available. The port may be in
use on a valid call. Use the status trunk command to determine when the port
is available for testing.
1004
ABORT
The port has been seized by a user for a valid call. Use the status trunk
command to determine when the port is available for testing.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1005
ABORT
Test failed due to incompatible configuration administered in trunk group form.
1. Look at the trunk group administration form and see whether the trunk is
1018
ABORT
Test has been disabled via administration.
1. Verify that the
2. Repeat the test.
1054
Issue 5 October 2002
Description/ Recommendation
incoming only, port 24 on a DS1 Interface with common control channel
signaling, or an automatic CO type such as FX. Under any of these
conditions this is a normal abort.
Maintenance Tests
set to n. To enable the test, issue the change trunk-group x command
where "x" equals the number of the trunk group to be tested. Then change
the entry in the
Maintenance Tests
field on the Trunk Group Form is
field on the form to y.
Continued on next page
555-233-119