DS1-BD (DS1 Interface Circuit Pack)
Table 225. TEST #53 SAKI Sanity Test — Continued
Error
Code
Test Result
1015
ABORT
2100
ABORT
1
FAIL
2
FAIL
PASS
0
NO BOARD
555-233-119
Description/ Recommendation
Port is not out-of-service.
1. Busyout the circuit pack.
2. Execute the command again.
System resources required for this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5 times.
The circuit pack failed to reset.
The circuit pack failed to restart.
1. Execute the command again.
2. If the problem persists, escalate this problem.
The circuit pack initializes correctly.
1. Run the Short Test Sequence.
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is inserted, an
incorrect board is inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the add
ds1 UUCSS command to administer the DS1 interface if it is not
already administered.
2. If board was already administered correctly, check the error log to
determine if the board is hyperactive. If this is the case, the board is
shut down. Reseating the board will re-initialize the board.
3. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port.
Continued on next page
Issue 5 October 2002
1083