Maintenance Objects
Tone Detector Audit/Update Test (#43)
A sanity audit is performed on the CLSFY-PT (Call Classifier Port).
Table 153. Tone Detector Audit/Update Test (#43)
Error
Test
Code
Result
none
ABORT
2000
ABORT
2100
ABORT
FAIL
PASS
896
Issue 5 October 2002
Description/ Recommendation
The system was not able to allocate all the resources needed for this test.
1. Wait 1 minute, and repeat the command a maximum of 5 times.
Response to the test request was not received within the allowable time
period.
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
Hardware audit failed.
1. Run the short test sequence with test port PCSSpp sh r 1.
2. If the problem persists, the system is still operating properly but system
capacity will be reduced. In order to restore system performance to
normal, replace the CLSFY-BD (Call Classifier circuit pack) containing
the defective CLSFY-PT (Call Classifier Port).
The (CLSFY-PT) Call Classifier Port has passed the sanity inquiry.