NPE Crosstalk Test (#6)
One or more NPEs reside on each circuit pack with a TDM Bus interface. The
NPE controls port connectivity and gain, and provides conferencing functions on a
per port basis. The NPE Crosstalk Test verifies that this port's NPE channel talks
on the selected time slot and never crosses over to time slots reserved for other
connections. If the NPE is not working correctly, one way and noisy connections
may be observed. This test is usually only part of a port's long test sequence and
takes approximately 20 to 30 seconds to complete.
Table 217. TEST #6 NPE Crosstalk Test
Error
Test
Code
Result
ABORT
1000
ABORT
1001
ABORT
1002
ABORT
1003
ABORT
1062
Issue 5 October 2002
Description/ Recommendation
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
System resources required to run this test are not available. The port may
be busy with a valid call. Use the display port PCSSpp command to
determine the trunk group/member number of the port. Use the status
trunk command to determine the service state of the port. If the service
state indicates that the port is in use, then the port is unavailable for certain
tests. You must wait until the port is idle before retesting.
1. If the port status is idle, then retry the command at 1-minute intervals a
maximum of 5 times.
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
The system could not allocate time slots for the test. The system may be
under heavy traffic conditions or it may have time slots out-of-service due to
TDM-BUS errors. Refer to TDM-BUS (TDM-Bus) Maintenance
documentation to diagnose any active TDM-BUS errors.
1. If system has no TDM-BUS errors and is not handling heavy traffic,
repeat test at 1-minute intervals a maximum of 5 times.
The system could not allocate a tone receiver for the test. The system may
be oversized for the number of tone detectors present or some tone
detectors may be out-of-service.
1. Look for TTR-LEV errors in the Error Log. If present, refer to TTR-LEV
Maintenance documentation.
2. Look for TONE-PT errors in the Error Log. If present, refer to TONE-PT
Maintenance documentation.
3. If neither condition exists, retry the test at 1-minute intervals a
maximum of 5 times.
Continued on next page