PKT-INT (Packet Interface)
Table 391. TEST #884 Memory Checksum Test
Error
Test
Code
Result
1006
ABORT
Packet Interface is in the out-of-service state so normal maintenance tests will
1137
not run.
1334
ABORT
The Packet Interface command queue is full. This should be a temporary
condition caused by a high rate of commands being sent to a Packet
Interface. Continued operation with a full command queue will cause a system
WARM restart that may escalate to more severe restart levels.
2000
ABORT
Response to the test request was not received within the allowable time
period.
2500
ABORT
Internal system error.
NO
The Packet Interface is not detected as being physically present.
BOARD
1537
FAIL
The Boot PROM memory checksum test failed. The Packet Interface may still
be operational.
555-233-119
Description/ Recommendation
1. Use the display system-parameters maintenance command to
identify which C-LAN circuit pack is administered with the Bus
Bridge. Verify that the C-LAN circuit pack is present and is not
alarmed.
2. Request a Packet Interface reset using the reset
packet-interface AS command. Refer to the Packet Interface
Reset Test (#889) repair procedures for further action.
1. Retry the command at 10-second intervals, a maximum of 5
times.
1. Retry the command at 1-minute intervals, a maximum of 3 times.
1. Retry the command.
1. Reboot the system, then retry the command. If the NO BOARD
indication persists, replace the TN2402/TN798 Processor circuit
pack.
1. Retry the command.
2. If the same error code occurs, replace the TN2402/TN798
Processor circuit pack at a time that would cause the least
disruption of service. The Packet Interface is still functional but
should be replaced since it may not operate after a system reboot
and it will enter a fatal fault state if it is reset for other reasons.
Continued on next page
Issue 5 October 2002