ISDN-TRK (DS1 ISDN Trunk)
Table 318. TEST #6 NPE Crosstalk Test — Continued
Error
Test
Code
Result
2020
ABORT
2100
ABORT
Any
FAIL
PASS
Conference Circuit Test (#7)
The Conference Circuit test verifies that the NPE channel for the port being tested
can correctly perform the conferencing function. The NPE is instructed to listen to
several different tones and conference the tones together. The resulting signal is
then measured by a tone detector port. If the level of the tone is within a certain
range, the test passes.
NOTE:
The TN464C or later UDS1 circuit pack has one SCOTCH-NPE chip instead
of several NPE chips.
Table 319. TEST #7 Conference Circuit Test
Error
Test
Code
Result
ABORT
1000
ABORT
555-233-119
Description/ Recommendation
The test did not run due to an already existing error on the specific port or a
more general circuit pack error.
1. Examine Error Log for existing errors against this port or the circuit pack
and attempt to diagnose the already existing error.
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
The NPE of the tested port was found to be transmitting in error. This will
cause noisy and unreliable connections. The ISDN-TRK is moved to
out-of-service/near-end state.
1. Replace the circuit pack.
The port is able to communicate over the TDM Bus.
Description/ Recommendation
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
System resources required to run this test are not available. The port may
be in use on a valid call. Use status station or status trunk commands to
determine when the port is available for testing.
Continued on next page
Continued on next page
Issue 5 October 2002
1317