Avaya DEFINITY Server CSI Maintenance Manual page 1736

Table of Contents

Advertisement

Maintenance Objects
Tone Generator Crosstalk Test (#90)
This test checks the ability of the Tone Generator to talk on a specific time slot.
The other idle time slots are checked to make sure the Tone Generator put the
tone on only the specified time slot.
Table 515. TEST #90 Tone Generator Crosstalk Test
Error
Test
Code
Result
None
ABORT
1001
ABORT
1002
ABORT
2000
ABORT
2100
ABORT
FAIL
PASS
1736
Issue 5 October 2002
Description/ Recommendation
Internal System Error
1. Retry the command at 1-minute intervals a maximum of 5 times.
The system was not able to put the tone generation facility in the
appropriate mode to test it.
The system could not allocate time slots for the test connection. This can
happen when the system is heavily loaded. If the system is not heavily
loaded, then test the TDM-BUS via the test tdm port-network PN#
command. Refer to TDM-BUS section for details.
Response to the test request was not received within the allowable time
period.
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
The Tone Generator could be defective.
1. Test the Tone-Clock circuit pack again via the test tone-clock PC
command
2. If the test fails again, look at the Hardware Error Log for Tone Detector
circuit pack errors.
3. If there are Tone Detector circuit pack errors, refer to Tone Detector
Maintenance documentation (DTMR-PT, GPTD-PT, CLAS-PT, ETR-PT)
to resolve these errors first.
4. If there are no Tone Detector circuit pack errors, then the Tone-Clock
circuit pack should be replaced. See
Circuit Pack''
in the TONE-BD section.
The tone generation facility is able to put tones out.
''How to Replace a Tone-Clock
Continued on next page