SW-CTL (Switch Control)
Time of Day Clock Test (#95)
The short term accuracy of the Time of Day (TIME-DAY) clock is tested. The test
reads the clock once, waits a short time, and reads the clock again. The second
reading of the clock must be within certain limits relative to the first reading for the
test to pass. The display time command can be used to display the current
setting of the TIME-DAY clock.
Table 459. TEST #95 Time of Day Clock Test
Error
Test
Code
Result
1000
ABORT
2012
ABORT
2013
ABORT
2001
FAIL
other
FAIL
PASS
555-233-119
Description/ Recommendation
The test was interrupted by a higher priority task.
1. Rerun the test at 1-minute intervals a maximum of 5 times.
2. If the test aborts 5 times, wait until the system is less heavily used and
rerun the test at that time.
Internal system error
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
The Time of Day clock could not be read.
1. Run the set time command and set the time to the current time.
2. Run the Short Test Sequence several times to determine if setting the
time corrected the error. Proceed to Step 3 if the error is still occurring.
3. Replace the Processor circuit pack at the customer's convenience.
The accuracy of Time of Day clock is not within limits.
1. Run the Short Test Sequence several times to make sure the error is
occurring consistently.
2. Replace the Network Control (DATA-BD) circuit pack at the customer's
convenience.
The Time of Day clock on the Switch Control circuit pack is operating
correctly.
Continued on next page
Issue 5 October 2002
1595