TBRI-BD (TN2185 ISDN Trunk-Side BRI)
Table 468. TBRI-BD Error Log Entries — Continued
Error
Aux
Type
Data
3840(l)
4096
to
4101
3842 (m)
46095
3843 (n)
46097
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Notes:
a. The circuit pack stopped functioning or is physically removed from the
system.
If the circuit pack is not in the system, insert a circuit pack in the same slot
as the error indicates. See note (g).
b. Transient communication problems between the switch and this circuit
pack. Execute the test board PCSS command and refer to the repair
procedures for the Control Channel Loop Around Test (#52).
c. On-board hardware failure. Aux data values correspond to the following
detected errors:
4352
4353
4355
4357
Reset the circuit pack with the busyout board PCSS and reset board
PCSS commands. When reset, the circuit pack executes a set of tests to
detect the presence of any of the faults listed above. Detection of one of
these errors during initialization causes the circuit pack to lock-up and
appear insane to the system. See the repair procedure in Note (a).
d. The circuit pack detects a program logic error. While no action is required,
this error can lead to other errors against this circuit pack.
555-233-119
Associated Test
NOTE:
This alarm logs approximately 11 minutes after removing the circuit
pack and/or the SAKI Sanity Test (#53) fails.
External RAM error
Internal RAM error
ROM Checksum error
Instruction set error
Alarm
On/Off
Level
Board
Continued on next page
Issue 5 October 2002
Test to Clear Value
1619