Maintenance Objects
Table 496. TEST #6 NPE Crosstalk Test — Continued
Error
Test
Code
Result
1000
ABORT
1001
ABORT
1002
ABORT
1003
ABORT
1004
ABORT
1682
Issue 5 October 2002
Description/ Recommendation
System resources required to run this test were not available. The port may
be busy with a valid call. Use the display port PCSSpp command to
determine the trunk group/member number of the port. Use the status
trunk command to determine the service state of the port. If the service
state indicates that the port is in use, then the port is unavailable for certain
tests. You must wait until the port is idle before retesting.
1. If the port status is active but the port is not in use (no calls), check the
error log for error type 1025 (see the error log table for a description of
this error and required actions). The port may be locked up.
2. If the port status is idle, retry the command at 1-minute intervals for a
maximum of 5 times.
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
The system could not allocate time slots for the test. The system may be
under heavy traffic conditions, or it may have time slots out of service due to
TDM-BUS errors. Refer to the TDM-BUS (TDM bus) Maintenance
Documentation to diagnose any active TDM-BUS errors.
1. If the system has no TDM-BUS errors and is not handling heavy traffic
and the port status is idle, retry the command at 1-minute intervals for a
maximum of 5 times.
The system could not allocate a tone receiver for the test. The system may
be oversized for the number of tone detectors present or some of the tone
detectors may be out of service. Issue the list measurements
tone-receiver command to display basic information about the system's
tone receivers.
1. Look for TTR-LEV errors in the error log. If present, refer to the
TTR-LEV Maintenance documentation.
2. Look for TONE-PT errors in the error log. If present, refer to the
TONE-PT Maintenance documentation.
3. If neither condition exists, retry the test at 1-minute intervals for a
maximum of 5 times.
The port was seized by a user for a valid call. Use the display port
PCSSpp command to determine the trunk group/member number of the
port. Use the status trunk command to determine the service state of the
port. If the service state indicates that the port is in use, then the port is
unavailable for certain tests. You must wait until the port is idle before
retesting.
1. If the port status is idle, retry the command at 1-minute intervals for a
maximum of 5 times.
Continued on next page