11.12 T: Auto-Tuning
If the amount of PG (pulse generator, encoder) Z-pulse offset is unknown, or the encoder has been replaced,
perform Z Pulse Offset Tuning and correct for the offset (Δθ) from the Z phase.

T3: ASR and Inertia Tuning

T3-00: Control Loop Tuning Selection
No.
Name
(Hex.)
T3-00
Control Loop Tuning
Selection
(1198)
0 : Inertia Tuning
1 : ASR Tuning
T3-01: Test Signal Frequency
No.
Name
(Hex.)
T3-01
Test Signal
Frequency
(0760)
Lower the setting value if the load inertia is too significant and a fault is detected after the Inertia Tuning.
T3-02: Test Signal Amplitude
No.
Name
(Hex.)
T3-02
Test Signal
Amplitude
(0761)
Lower the setting value if the load inertia is too significant and a fault is detected after the Inertia Tuning. Adjust
this parameter if a fault occurs when T3-01 [Test Signal Frequency] is set to a low value.
T3-03: Motor Inertia
No.
Name
(Hex.)
T3-03
Motor Inertia
(0762)
The default setting is for a Yaskawa standard motor as listed in the motor inertia table. Actual values vary
depending on whether the motor used is an induction motor or a PM motor.
Note:
Capacities below 37 kW are set in units of 0.0001 kgm
T3-04: System Response Frequency
No.
Name
(Hex.)
T3-04
System Response
Frequency
(0763)
Oscillation may result if the value input here is too high.

T4: EZ Tuning

With the T4 parameters, the data required for motor parameter auto-tuning is input when setting A1-02 = 8
[Control Method Selection = EZ Open Loop Vector Control]. The following two modes are available.
922
V/f
CL-V/f
OLV
CLV
AOLV
Selects the Control Auto-Tuning method to be used.
V/f
CL-V/f
OLV
CLV
AOLV
Normally there is no need to change this setting. Sets the frequency of the
test signal applied to the motor during Inertia Tuning.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amplitude of the test signal applied to the motor during Inertia
Tuning. Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the inertia of the motor. This value is used to determine the load inertia
using the test signal response.
2
. Capacities 37 kW and above are set in units of 0.001 kgm
V/f
CL-V/f
OLV
CLV
AOLV
C5-01 [ASR Proportional Gain 1] is automatically calculated and set using
the load inertia value derived by the Inertia Tuning process.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0 - 1)
Default Setting
(Range)
3.0 Hz
(0.1 - 20.0 Hz)
Default Setting
(Range)
0.5 rad
(0.1 - 10.0 rad)
Default Setting
(Range)
Determined by o2-04,
C6-01, and E5-01
(0.0001 - 6.0000
kgm
2
)
2
.
Default Setting
(Range)
10.0 Hz
(0.1 - 50.0 Hz)