YASKAWA GA700 Technical Manual page 594

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.3 b: Application
Refer to the instruction manual included with the option card for installing and setting the option card.
Note:
If b1-01 = 3 is set and an option card is not connected, then oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the keypad.
4 : Pulse train input
Use a pulse train signal from the pulse train input terminal RP to enter the frequency reference.
Follow the procedure below to make sure that the pulse train signal is functioning properly.
1. Set b1-01 = 4, H6-01 = 0 [PulseTrain InTerm RP Func Select = Frequency reference].
2. Set H6-02 [Pulse Train Input Scaling] to the number of pulses that determine 100% of the frequency
reference.
3. Enter a pulse train signal on the terminal RP and make sure that the keypad shows a correct frequency
reference.
b1-02: Run Command Selection 1
No.
Name
(Hex.)
b1-02
Run Command
Selection 1
(0181)
0 : Keypad
Use the keypad to enter the Run command.
The user can execute the JOG operation or the FWD/REV commands from the keypad.
Note:
The LO/RE light will light when the Run command source is set to the keypad.
1 : Digital Input
Use the control circuit terminals to enter the Run command. Select the input method for the Run command using a
parameter. Set H1-xx = 0, 40 to 43 [3-Wire Sequence, Run Command (2-Wire Sequence)]. The default setting is
2-wire sequence 1.
• 2-wire Sequence 1
This sequence allows for two types of input: FWD/Stop and REV/Stop. Setting A1-03 = 2220 [Initialize
Parameters = 2-Wire initialization] and initializing the drive sets terminals S1 and S2 for a 2-wire sequence.
• 2-wire Sequence 2
This sequence allows for two types of input: Run/Stop and FWD/REV.
• 3-Wire Sequence
This sequence allows for three types of input: Run, Stop, and FWD/REV. Setting A1-03 = 3330 [Initialize
Parameters = 3-Wire initialization] and initializing the drive sets terminals S1, S2, and S5 for a 3-wire
sequence.
2 : Memobus/Modbus Communications
Enter the Run command by using MEMOBUS/Modbus communications.
3 : Option PCB
Use a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card for installation and communications settings.
Note:
If b1-02 = 3 is set and an option card is not connected, then oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the keypad.
b1-03: Stopping Method Selection
No.
Name
(Hex.)
b1-03
Stopping Method
Selection
(0182)
Note:
The setting range is 0, 1, and 3 when A1-02 = 3, 4, 5, 6, 7, or 8 [Control Method Selection = Closed Loop Vector Control, Advanced
OpenLoop Vector Control, PM Open Loop Vector Control, PM Advanced Open Loop Vector, PM Closed Loop Vector Control, or EZ
Open Loop Vector Control].
594
V/f
CL-V/f
OLV
CLV
AOLV
Selects the Run command input method.
V/f
CL-V/f
OLV
CLV
AOLV
Selects how the drive stops the motor after removing a Run command or
entering a Stop command.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
1
(0 - 3)
Default Setting
(Range)
0
(0 - 3)