No.
Name
(Hex.)
H3-13
Analog Input
FilterTime
(041B)
Constant
H3-14
Analog Input
Terminal Enable
(041C)
Sel
H3-16
Terminal A1 Offset
(02F0)
H3-17
Terminal A2 Offset
(02F1)
H3-18
Terminal A3 Offset
(02F2)
H3-40
Extend MFAI1
Function Selection Selects the MEMOBUS AI1 function.
(0B5C)
H3-41
Extend MFAI2
Function Selection Selects the MEMOBUS AI2 function.
(0B5F)
H3-42
Extend MFAI3
Function Selection Selects the MEMOBUS AI3 function.
(0B62)
H3-43
Filter Time for
MFAI
(117F)
H3-xx: Multi-Function Analog In Setting Value
Setting
Function
0
Frequency
BiasMaster
frequency
reference
1
Frequency Gain
2
Auxiliary
Frequency
Reference 1
3
Auxiliary
Frequency
Reference 2
4
Output Voltage
Bias
5
Accel/Decel Time
Gain
6
DC Injection
Braking Current
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant when applying a primary delay filter to the
MFAI terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the enabled terminal Sx when H1-xx = C [Terminal Sx
Function Selection = Analog Terminal Enable Selection] is ON.
Also selects the disabled terminal Sx when the input is OFF.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for the analog signal input to terminal A1.
Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A2.
Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A3.
Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant when applying a primary delay filter to the
MEMOBUS analog input terminal.
V/f
CL-V/f
OLV
CLV
AOLV
The input value from the analog input terminal set with this function becomes the master
frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
The input value from the analog input terminal set with this function is multiplied by the
analog frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
When Reference 2 is selected via multi-step speed reference, the command reference
(Auxiliary Frequency Reference 1) from the analog input terminal set with this setting is
enabled. Set E1-04 [Maximum Output Frequency] as 100%.
V/f
CL-V/f
OLV
CLV
AOLV
When Reference 3 is selected via multi-step speed reference, the command reference
(Auxiliary Frequency Reference 2) from the analog input terminal set with this setting is
enabled. Set E1-04 [Maximum Output Frequency] as 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Set this parameter to input a bias signal that amplifies the output voltage.
V/f
CL-V/f
OLV
CLV
AOLV
Inputs the signal that adjusts the gain used for C1-01 through C1-08 [Accel & Decel Time
1 through 4] assuming that the full scale analog signal (10 V or 20 mA) is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Inputs the signal that adjusts the current level used for DC Injection Braking assuming
that the drive rated output current is 100%.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.10 H: Terminal Functions
Default
Ref.
(Range)
0.03 s
805
(0.00 - 2.00 s)
7
805
(1 - 7)
0
806
(-500 - +500)
0
806
(-500 - +500)
0
806
(-500 - +500)
F
806
(4 - 2F)
F
806
(4 - 2F)
F
807
(4 - 2F)
0.00 s
807
(0.00 to 2.00 s)
Ref.
807
807
807
807
808
808
808
10