b1-08: Run Command Select in PRG Mode
No.
Name
(Hex.)
b1-08
Run Command Select
in PRG Mode
(0187)
For safety purposes, the default setting is to disregard the Run command while in the Programming Mode.
This parameter prevents accidents that might otherwise occur from the motor suddenly rotating when the Run
command is entered from an external source while the user is programming the drive.  The user can also set the
drive so that the keypad won't display the Programming Mode as long as the Run command is active.
Note:
The Programming Mode has the following modes.
• Verify Menu
• Setup Mode
• Parameter Settings Mode
• Auto-Tuning Mode
0 : Do not accept RUN at Programming
The drive does not accept the Run command while in the Programming Mode.
1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source while in the Programming Mode.
2 : Allow Programming only at Stop
The drive does not allow the user to enter the Programming Mode while the Run command is enabled. The
keypad does not display the Programming Mode while the Run command is enabled.
b1-14: Phase Order Selection
No.
Name
(Hex.)
b1-14
Phase Order
Selection
(01C3)
0 : Standard
1 : Switch phase order
b1-15: Frequency Reference Selection 2
No.
Name
(Hex.)
b1-15
Frequency Reference
Selection 2
(01C4)
Enabled when H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection] is set and switched ON.
Note:
• Set the input mode to LOCAL by pressing
• The RUN light on the keypad will flash if the Run command is entered when the frequency reference is 0 Hz or equal to or below the
value set in E1-09 [Minimum Output Frequency]. Check the setting for the frequency reference input and enter a value greater than or
equal to what is set in E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Change the frequency reference by using
1 : Analog Input
Use the multi-function analog input terminals A1, A2, and A3 to input an analog frequency reference with a
voltage or current input signal.
• Voltage Input
600
V/f
CL-V/f
OLV
CLV
AOLV
Sets the conditions for the drive to accept a Run command entered from an
external source when using the keypad to set parameters.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This
parameter is useful for making sure the Forward Run command from the
drive and the forward direction of the motor match, without needing to
change any wiring.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the input method for frequency reference 2.
on the keypad to enter the frequency reference from the keypad.
and
on the keypad.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0 - 2)
Default Setting
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 4)