2.13 Wiring Procedure for the Main Circuit Terminal Block
3.
Tighten the screws to the specified torque.
4.
Check the signal from the wired terminal and use a nipper to clip the cutaway section of the corresponding
wiring cover.
Use a nipper to clip the areas shown in the following figure.
A - Cutaway section
Note:
• The shape of the wiring cover differs depending on the drive model.
• Detach the cutaway section of the wiring cover by clipping only the areas that apply to the wired terminal. If areas that do
not apply to the wired terminal are clipped, the protective enclosure will not maintain the IP20 protective level.
• When clipping the cutaway section of the wiring cover, firmly hold the cutaway section so that the section does not fly out,
then cut it. The cutaway section may fly out resulting in injury.
• Process the cross section to prevent the cutaway section of the wiring cover from damaging the electric wires.
• If electrical wires other than those specified by Yaskawa are used, the protective enclosure may not maintain the IP20
protective level, even if the wiring cover is used correctly. Contact Yaskawa or your nearest sales representative for details.
5.
Install the wiring cover at its original position. Pass the cables through the holes that were cut out of the
cable cover.
6.
Install the front cover and the keypad at their original positions.
70
Figure 2.40 Tighten Terminal Block Screws
Figure 2.41 Clip the Cutaway Section of the Wiring Cover
Figure 2.42 Reattach the Wiring Cover