YASKAWA GA700 Technical Manual page 660

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.4 C: Tuning
C5-08: ASR Integral Limit
No.
Name
(Hex.)
C5-08
ASR Integral Limit
(0222)
C5-12: Integral Operation @ Accel/Decel
No.
Name
(Hex.)
C5-12
Integral Operation @
Accel/Decel
(0386)
Enabling integral operation when driving a heavy load or a high inertia load may cause problems with overshoot
or undershoot at the end of acceleration and deceleration. Set C5-12 = 0 if there are problems of overshooting and
undershooting.
0 : Disabled
Integral operation is not enabled during acceleration or deceleration. Integral operation is always enabled during
constant speed.
1 : Enabled
Integral operation is always enabled.
C5-17: Motor Inertia
No.
Name
(Hex.)
C5-17
Motor inertia
(0276)
When A1-02 = 3 or 7 [Control Method Selection = Closed Loop Vector Control or PM Closed Loop Vector
Control], C5-17 is automatically set the value of [Motor Inertia] when any of the following Auto-Tuning
processes are executed.
• Inertia Tuning
• ASR Tuning
C5-18: Load Inertia Ratio
No.
Name
(Hex.)
C5-18
Load Inertia Ratio
(0277)
vWhen A1-02 = 3 or 7 [Control Method Selection = Closed Loop Vector Control or PM Closed Loop Vector
Control], C5-18 is automatically set to the load inertia ratio when any of the following Auto-Tuning processes are
executed.
• Inertia Tuning
• ASR Tuning
C5-21: Motor 2 ASR Proportional Gain 1
No.
Name
(Hex.)
C5-21
Motor 2 ASR
Proportional Gain 1
(0356)
RUN
The speed response increases with the weight of the load. Normally, the gain increases with larger loads.
Excessive gain causes vibration.
660
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit for ASR as a percentage of the rated load.
V/f
CL-V/f
OLV
CLV
AOLV
Enables or disables integral operation during acceleration and deceleration.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor inertia.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the load inertia ratio for the motor inertia.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to adjust ASR response.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
400%
(0 - 400%)
Default
(Range)
0
(0, 1)
Default
(Range)
Determined by o2-04,
C6-01, and E5-01
(0.0001 - 600.00
kgm
2
)
Default
(Range)
1.0
(0.0 - 6000.0)
Default
(Range)
Determined by E3-01
(0.00 - 300.00)