Protect Drive At Failure; Factory Recommended Branch Circuit Protection - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

2.23

Protect Drive at Failure

Factory Recommended Branch Circuit Protection

To maintain compliance with UL61800-5-1, execute branch circuit protection when a short occurs in the internal
circuit. Yaskawa recommends connecting a semiconductor protective type fuses to the input side for branch circuit
protection. Refer to
Table 2.27
NOTICE: Do not energize the power or operate equipment soon after a fuse blows or the circuit breaker (ELCB) trips. Check the
condition of cable wiring and peripheral devices to identify the root cause. If the root cause cannot be determined, do not turn on
the power or operate equipment. Contact Yaskawa Support immediately.
• 200 V class
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes
and 240 Vac during short circuit of the power supply, when protected by fuses as specified in this document.
• 400 V class
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes
and 480 Vac during short circuit of the power supply, when protected by fuses as specified in this document.
Drive's built-in short circuit protection does not provide branch circuit protection. Branch circuit protection must
be provided in accordance with the NEC (National Electric Code) the CEC (Canadian Electric Code, Part I), and
any additional local codes.
Three-Phase 200 V Class
Table 2.27 Factory Recommended Drive Branch Circuit Protection (Normal Duty)
Drive Model
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
*1
2082
*1
2110
*1
2138
*1
2169
*1
2211
*1
2257
*1
2313
*1
2360
*1
2415
*1
*1
Approval pending. Contact Yaskawa or your nearest sales representative.
*2
Fuses with larger rated currents are recommended for application with repetitive operations.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
to
Table 2.30
for the recommended fuses.
Maximum Applicable Motor
Output
kW (HP)
0.75 (0.75)
1.1 (1.5)
1.1 (1.5)
2.2 (3)
3 (4)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
-

2.23 Protect Drive at Failure

Semiconductor Fuse Model
Input Current Rating
A
4.8
6.7
6.7
12.7
17
20.7
30
40.3
52
78.4
96
114
111
136
164
200
271
324
394
-
Manufacturer: EATON/
Bussmann
FWH-45B
FWH-45B
FWH-45B
FWH-45B
FWH-100B
FWH-100B
FWH-100B
FWH-125B
FWH-150B
FWH-200B
FWH-225A
FWH-225A
FWH-250A
*2
FWH-225A
FWH-250A
*2
FWH-275A
FWH-300A
*2
FWH-275A
FWH-350A
*2
FWH-325A
FWH-450A
*2
FWH-600A
FWH-800A
FWH-1000A
FWH-1400A