Refer to the following table when using a voltage signal input to one of the multi-function analog input
terminals.
Terminal Signal
Terminal
Level
A1
0 - 10 V
-10 - +10 V
A2
0 - 10 V
-10 - +10 V
A3
0 - 10 V
-10 - +10 V
Figure 11.22 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1
Note:
Use this diagram also when wiring terminals A2 and A3.
• Current Input
Refer to the following table when using a current signal input to one of the multi-function analog input
terminals.
Terminal
Signal Level
A1
4 - 20 mA
0 - 20 mA
A2
4 - 20 mA
0 - 20 mA
A3
4 - 20 mA
0 - 20 mA
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Table 11.20 Frequency Reference Voltage Input
Parameter Settings
Signal Level
Function
Selection
Selection
H3-01 = 0
H3-02 = 0
[Frequency Bias]
H3-01 = 1
H3-09 = 0
H3-10 = 0
[Frequency Bias]
H3-09 = 1
H3-05 = 0
H3-06 = 0
[Frequency Bias]
H3-05 = 1
Parameter Settings
Signal Level
Function
Selection
Selection
H3-01 = 2
H3-02 = 0
[Frequency Bias]
H3-01 = 3
H3-09 = 2
H3-10 = 0
[Frequency Bias]
H3-09 = 3
H3-05 = 2
H3-06 = 0
[Frequency Bias]
H3-05 = 3
11.3 b: Application
Gain
Bias
H3-03
H3-04
H3-11
H3-12
H3-07
H3-08
Gain
Bias
H3-03
H3-04
H3-11
H3-12
H3-07
H3-08
Note
Set DIP switch
S1-1 to "V" for
voltage input.
Set DIP switch
S1-2 to "V" for
voltage input.
Set DIP switch
S1-3 to "V" for
voltage input.
Set DIP switch S4
to "AI" for analog
input.
Note
Set DIP switch
S1-1 to "I" for
current input.
Set DIP switch
S1-2 to "I" for
current input.
Set DIP switch
S1-3 to "I" for
current input.
Set DIP switch S4
to "AI" for analog
input.