11.8 H: Terminal Functions
11: Down Command
Setting
Function
11
Down Command
ON : Lowers the frequency reference.
OFF : Holds the current frequency reference.
Note:
• If only one of either the Up command or Down command has been set, oPE03 [Multi-Function Input Setting Err] will be detected.
• If two or more of the following functions have been allocated at the same time, oPE03 occurs.
–Up/Down command
–Accel/Decel Ramp Hold
–Reference sample hold
–Offset Frequency 1, 2, 3 addition
–Up/Down 2 Command
• The Up/Down command can be used when the keypad is in REMOTE mode or b1-01 ≠ 0 [Frequency Reference Selection 1 ≠
Keypad].
• The Up/Down command does not function when switching to parameter b1-15 [Frequency Reference Selection 2] using External
Reference 1/2 Selection [H1-xx = 2].
If the Up command is input, the frequency reference increases, and if Down command is input, the frequency
reference decreases.
Up and Down command has priority over all other frequency references. When the Up/Down command is
enabled, the following frequency references will be disregarded.
• Frequency reference from Keypad [b1-01 = 0]
• Frequency reference from Analog Input [b1-01 = 1]
• Frequency reference from Pulse Train Input [b1-01 = 4]
12: Forward Jog
Setting
Function
12
Forward Jog
Note:
• There is no need to input the Run command.
• The Forward JOG command has priority over all other frequency references.
• The drive performs ramp to stop when the Forward JOG and Reverse JOG commands have been turned ON at the same time for 500
ms or more.
13: Reverse Jog
Setting
Function
13
Reverse Jog
762
V/f
CL-V/f
OLV
CLV
AOLV
It is paired with setting value 10 (Up command). When using the Up command and Down
command, the user can raise and lower the frequency reference of the drive using two push buttons.
V/f
CL-V/f
OLV
CLV
AOLV
Inputting the Forward JOG command runs the motor in the forward direction at the jog frequency
set in d1-17 [Jog Reference].
Figure 11.77 JOG Operation Pattern
V/f
CL-V/f
OLV
CLV
AOLV
Inputting the Reverse JOG command reverses the motor at the jog frequency set in d1-17 [Jog
Reference].
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM