H2: Multi-Function Digital Output - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
7E: FWD/REV Detect (V/f w/ simplePG)
Setting
Function
7E
FWD/REV Detect
(V/f w/ simplePG)
ON : Reverse
Recognizes if the motor is rotating in the reverse direction.
OFF : Forward
Recognizes if the motor is rotating in the forward direction.
90 to 97: DriveWorksEZ Digital Inputs 1 to 8
Setting
Function
90 to 97
DriveWorksEZ
Digital Inputs 1 to 8
Note:
The setting values 90 to 97 cannot be set for inversion input.
9F: DriveWorksEZ Disable
Setting
Function
9F
DriveWorksEZ
Disable
Note:
This function can only be used when A1-07 = 2 [DriveWorksEZ Function Selection = Digital input].
ON : Disabled
OFF : Enabled

H2: Multi-function digital output

H2 parameters are used to configure MFDO terminals.
H2-01 through H2-04 Function selection for terminals M1-M2, M3-M4, P1-C1, and P2-
C2
This product is equipped with four MFDO terminals. The following table lists the functions according to the
default settings.
No.
H2-01
H2-02
H2-03
H2-04
Refer to the following table when configuring H2-xx [MFDO Function Select].
Setting
0
1
2
776
V/f
CL-V/f
OLV
CLV
Allows the rotation direction of the motor to be set when F1-21, F1-37 = 0 [Encoder Option
Function Selection = A pulse detection] for Simple Closed Loop V/f Control method and Closed
Loop V/f Control method.
V/f
CL-V/f
OLV
CLV
A setting parameter for digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ Online
Manual for more details.
V/f
CL-V/f
OLV
CLV
Enables and disables the DriveWorksEZ program that is saved in the drive.
Name
Terminal M1-M2 Function Select
(contact)
Terminal M3-M4 Function Select
(contact)
Terminal P1-PC Function Select
(open-collector)
Terminal P1-PC Function Select
(open-collector)
Table 11.50 MFDO setting value
Function
During Run
Zero Speed
Speed Agree 1
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Default Setting
0
1
2
F
Setting
3
4
5
Function
During Run
Zero Speed
Speed Agree 1
Through Mode
Function
User-set Speed Agree 1
Frequency Detection 1
Frequency Detection 2

Advertisement

Table of Contents
loading

Table of Contents