2.15 Control I/O Connections
DIP Switch Settings
Termi
Input
nal
Signal
Switch
Voltage
input
A3
S1-3
Current
input
Note:
• To set both A1 and A2 to frequency reference, set H3-02, H3-10 = 0 [Terminal A1 Function Selection, Terminal A2 Function Selection
= Frequency Bias]. Both analog input values will be combined to create the frequency reference.
• To set DIP switches, use tweezers or a jig that has a tip of approximately 0.8 mm.
• To use terminal A3 as an analog input (voltage/current) terminal, set DIP switch S4 to "AI." The default setting of DIP switch S4 is
"AI."
◆
Select Input Signal for Terminal A3 of Multi-Function Analog Input
Terminal A3 can be configured either as multi-function analog input, or as PTC input for motor overload
protection.
Set using DIP switch S4.
Terminal
A3
◆
Select Output Signals for FM, AM Terminals of Multi-function Analog Monitor
Output
Terminals FM and AM can be used to output either a voltage or a current signal. Set this using jumper switch S5
and H4-07, H4-08.
82
Setting
No.
V
0: 0 V to 10 V/100% (input impedance: 20 kΩ)
(Default
1: -10 V to 10 V/-100% to 100%
setting)
H3-05
2: 4 mA to 20 mA/100%
I
3: 0 mA to 20 mA/100% (input impedance: 250 Ω)
Figure 2.56 Location of DIP Switch S4
Settings for DIP
Switches
AI
Functions as multi-function analog input terminal.
(Default setting)
Select function using H3-06.
Functions as PTC input terminal.
PTC
Set H3-06 = E [Motor Temperature (PTC input)].
Set S1-3 to "V" for voltage input.
Figure 2.57 Location of Jumper Switch S5
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Parameters
Signal Level
Description