Configure a unique slave address that does not conflict with other slave devices.
H5-02: Communication Speed Selection
No.
Name
(Hex.)
H5-02
Communication
Speed Selection
(0426)
Note:
Restart the drive to enable the settings.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
H5-03: Communication Parity Selection
No.
Name
(Hex.)
H5-03
Communication
Parity Selection
(0427)
Note:
Restart the drive to enable the settings.
0 : No parity
1 : Even parity
2 : Odd parity
H5-04: Stopping Method after Com Error
No.
Name
(Hex.)
H5-04
Stopping Method
after Com Error
(0428)
0 : Ramp to stop
The drive ramps the motor to stop according to the deceleration time. The terminal turns on when H2-xx = E
[MFDO Function Select = Fault] is set.
1 : Coast to stop
The drive shuts off output and the motor coasts to stop. The terminal turns on when H2-xx = E.
2 : Fast Stop (use C1-09)
The drive stops the motor using the deceleration time set in C1-09 [Fast Stop Time]. The terminal turns on when
H2-xx = E.
3 : Alarm only
CE appears on the keypad, and operation continues.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Selects the communications speed for MEMOBUS/Modbus
communications.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the communications parity used for MEMOBUS/Modbus
communications.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the motor Stopping Method when CE [MEMOBUS/Modbus
Communication Err] issues are detected.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: Terminal Functions
Default
(Range)
3
(0 - 8)
Default
(Range)
0
(0 - 2)
Default
(Range)
3
(0 - 3)
11
817