11.12 T: Auto-Tuning; T0: Tuning Mode Selection; T1: Inductionmotor Auto-Tuning - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.12 T: Auto-Tuning

11.12 T: Auto-Tuning
Numbers identifying the T parameters are displayed when an LED keypad is used. The names of the parameters
are displayed on the LCD screen of the LCD keypad. Set the following.
• Induction Motor Auto-Tuning
• PM Motor Auto-Tuning
• ASR and Inertia Tuning

T0: Tuning Mode Selection

T0-00: Tuning Mode Selection
Select T0-00 first when the control mode used supports Control Tuning. Then, select the motor to be tuned by T1-
00 [Motor 1/Motor 2 Selection] and the tuning mode by T2-01 [PM Motor Auto-Tuning Mode Select] or T3-00
[Control Loop Tuning Selection].
No.
Name
(Hex.)
T0-00
Tuning Mode
Selection
(1197)
0 : Motor Parameter Tuning
1 : Control Tuning
Note:
The available tuning modes vary depending on the control mode.

T1: InductionMotor Auto-Tuning

T1 parameters set the Auto-Tuning input data for induction motor tuning.
Note:
• The base frequency of drive dedicated motors and special motors for use with vector control may be lower than the base frequency of
general-purpose motors, which is 50 Hz or 60 Hz. In such cases, this lower frequency is used as the value for E1-06 [Base Frequency]
and E1-04 [Maximum Output Frequency] after Auto-Tuning completes. If the maximum output frequency is too low and causes
problems, change the setting of E1-04 after Auto-Tuning completes.
• The following induction motor parameters are set automatically.
–E1-xx [V/f Pattern for Motor 1]
–E2-xx [Motor Parameters]
–E3-xx [V/f Pattern for Motor 2]
–E4-xx [Motor 2 Parameters]
–F1-xx [Encoder Options] (only with Closed Loop Vector Control)
T1-00: Motor 1/Motor 2 Selection
No.
Name
(Hex.)
T1-00
Motor 1/Motor 2
Selection
(0700)
Note:
This parameter can be set when H1-xx = 16 [Motor 2 Selection] is ON and is not displayed when H1-xx = 16 is OFF. Motors cannot be
switched via external input. Use the keypad to display T1-00 and change the setting value to switch the motor.
1 : Motor 1 (sets E1-xx, E2-xx)
Auto-Tuning automatically sets parameters E1-xx and E2-xx for motor 1.
2 : Motor 2 (sets E3-xx, E4-xx)
Auto-Tuning automatically sets parameters E3-xx and E4-xx for motor 2. Make sure that motor 2 is connected to
the drive for Auto-Tuning.
916
V/f
CL-V/f
OLV
CLV
AOLV
Selects the type of Auto-Tuning to be used.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the motor to be tuned when motor 1/2 switching is enabled. This
parameter can only be set via the keypad not via external input terminals.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0, 1)
Default
(Range)
1
(1, 2)